DB37/T 3514-2019 煤矿在用电力变压器电气安全检测检验规范
DB37/T 3514-2019 The safety inspection and testing specifications for electrical equipment used in coal mines
基本信息
发布历史
-
2019年03月
研制信息
- 起草单位:
- 起草人:
- 出版信息:
- 页数:13页 | 字数:- | 开本: -
内容描述
ICS29.180
K41
DB37
山东省地方标准
DB37/T3514—2019
煤矿在用电力变压器电气安全检测检验规
范
2019-03-21发布2019-04-21实施
山东省市场监督管理局发布
DB37/T3514—2019
目次
前言...............................................................................III
1范围...............................................................................1
2规范性引用文件.....................................................................1
3检验一般要求.......................................................................1
4检验项目及检验周期.................................................................1
5技术要求...........................................................................3
5.1外观、证件检查.................................................................3
5.2绕组绝缘电阻和吸收比或极化指数.................................................3
5.3绕组泄漏电流...................................................................3
5.4绕组连同套管的介质损耗角正切值tgδ及电容量.....................................4
5.5非纯瓷套管的介质损耗角正切值tgδ................................................4
5.6有载调压装置的检查和试验.......................................................5
5.7绕组直流电阻...................................................................5
5.8测温装置检查及二次回路绝缘电阻测量.............................................5
5.9气体继电器检查及二次回路绝缘电阻测量...........................................5
5.10铁芯绝缘电阻..................................................................5
5.11电压比........................................................................6
5.12组别和极性....................................................................6
5.13绕组连同套管的交流耐压试验....................................................6
5.14检查相位......................................................................6
5.15冲击合闸试验..................................................................6
5.16绝缘油........................................................................6
5.17油中溶解气体色谱分析..........................................................6
6检验方法...........................................................................6
6.1外观、证件检查.................................................................6
6.2绕组绝缘电阻...................................................................7
6.3绕组泄漏电流...................................................................7
6.4介质损耗角正切值tgδ及电容量...................................................7
6.5有载调压装置的检查和试验.......................................................8
6.6二次回路的绝缘电阻.............................................................8
6.7绕组直流电阻...................................................................8
6.8铁芯绝缘电阻...................................................................8
6.9电压比.........................................................................8
6.10组别和极性....................................................................8
6.11交流耐压试验..................................................................8
I
DB37/T3514—2019
6.12检查相位......................................................................8
6.13冲击合闸试验..................................................................9
6.14绝缘油........................................................................9
6.15油中溶解气体色谱分析..........................................................9
7检验规则...........................................................................9
8判定规则...........................................................................9
II
DB37/T3514—2019
前言
本标准按照GB/T1.1—2009给出的规则起草。
本标准由山东省安全生产监督管理局提出并监督实施。
本标准由山东省安全生产标准化技术委员会归口。
本标准起草单位:山东公信安全科技有限公司。
本标准主要起草人:张振安、荀明利、李旗、宋宪旺、张艳会、郭英俊、徐士伟。
本标准为首次发布。
III
DB37/T3514—2019
煤矿在用电力变压器电气安全检测检验规范
1范围
本标准规定了煤矿在用电力变压器电气安全检测检验一般要求、检验项目及检验周期、技术要求、
检验方法、检验规则和判定规则。
本标准适用于煤矿6kV及以上的地面、井下在用电力变压器的定期检测检验、新安装投运前及交接
验收检验。
本标准不适用于产品出厂检验、大修后检验。
2规范性引用文件
下列文件对于本文件的应用是必不可少的。凡是注日期的引用文件,仅所注日期的版本适用于本文
件。凡是不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
DL/T722变压器油中溶解气体分析和判断导则
GB/T7595运行中变压器油质量
《煤矿安全规程》国家安全生产监督管理总局煤矿安全监察局
3检验一般要求
3.1所检电力变压器应为处于运行状态的或新安装拟投入使用的设备。
3.2检验现场环境温度应不低于5℃,空气相对湿度应不高于85%。
3.3井下检验,使用电气仪表时应满足《煤矿安全规程》规定。
3.4检验井下电力变压器时,应对现场环境进行监测,环境条件应符合《煤矿安全规程》规定。
4检验项目及检验周期
4.1定期检验项目及检验周期见表1、表2。
表1油浸式电力变压器定期检验项目及检验周期
序号检验项目检验周期说明
1外观、证件检查1年
所有变压器均应测量绝缘电阻,电压35kV及以上或容
绕组绝缘电阻、吸收比或(和)极化
21年量4000kVA及以上的应同时测量吸收比,电压110kV
指数
及以上或容量8000kVA及以上的应同时测量极化指数。
3绕组泄漏电流1年容量315kVA及以下或电压1.2kV以下不做此项试验。
绕组连同套管的介质损耗角正切值电压35kV及以上或容量1000kVA及以
定制服务
推荐标准
- DB35/T 1472-2014 工业锅炉表面散热损失红外热像测试方法 2014-12-29
- DB35/T 1483-2014 菌草栽培技术规范 2014-12-29
- DB35/T 1478-2014 生态公益林林分修复技术规程 2014-12-29
- DB35/T 1481-2014 仿刺参南方度夏养殖技术规范 2014-12-29
- DB35/T 754-2014 摩托车和轻便摩托车化油器质量评定 2014-12-29
- DB35/T 1486-2014 海水中稀土元素的测定 电感耦合等离子体质谱法 2014-12-29
- DB35/T 1477-2014 地理标志产品 吉山老酒 2014-12-29
- DB35/T 1467-2014 用于水泥和混凝土中的铅锌铁尾矿微粉 2014-10-30
- DB35/T 557-2014 真姬菇工厂化栽培技术规范 2014-12-29
- DB35/T 1484-2014 菌草栽培灵芝技术规范 2014-12-29