内容描述
ICS91.040.01
P18DB1331
雄安新区地方标准
DB1331/T033-2022
雄安新区食品站药品站
设计标准
Designstandardforfoodstationanddrugstation
inXiong'anNewArea
2022-10-25发布2022-11-01实施
河北雄安新区管理委员会改革发展局
发布
河北雄安新区管理委员会规划建设局
雄安新区地方标准
雄安新区食品站药品站
设计标准
Designstandardforfoodstationanddrugstation
inXiong'anNewArea
DB1331/T033-2022
主编单位:河北雄安新区管理委员会规划建设局
中国建筑标准设计研究院有限公司
批准部门:河北雄安新区管理委员会改革发展局
施行日期:2022年11月1日
2022北京
1
雄安新区地方标准
雄安新区食品站药品站设计标准
Designstandardforfoodstationanddrugstation
inXiong'anNewArea
DB1331/T033-2022
*
出版(北京市海淀区三里河路1号)
***********有限公司印刷
*
开本:850mm×1168mm1/32印张:1.656字数:13千字
20XX年X月第X版20XX年XX月第1次印刷
印数:1~3000册定价:XX.00元
统一书号:XXX·XXX
版权所有翻印必究
2
河北雄安新区管理委员会改革发展局
通告
2022年第8号
河北雄安新区管理委员会改革发展局
关于发布《雄安新区变配电站规划设计规范》等
四项雄安新区地方标准的通告
河北雄安新区管理委员会改革发展局组织制定了《雄安新区
变配电站规划设计规范》等3项雄安新区地方标准,会同河北雄
安新区管理委员会规划建设局联合发布了《雄安新区食品站药品
站设计标准》1项雄安新区地方标准,现予以通告(详细目录见
附件)。
本通告可通过中国雄安官网()“政务信
息”中进行查询,标准文本可从标准图书馆网站
()中下载。
河北雄安新区管理委员会改革发展局
2022年10月25日
3
前言
本标准根据河北雄安新区管理委员会改革发展局《关于印发
雄安新区地方标准立项项目计划的通知》的要求,由河北雄安新
区管理委员会规划建设局组织编制,项目编号:GCJS202102。
本标准共7章和1个附录,主要技术内容包括:1.总则;2.
术语;3.建筑;4.采暖通风与空气调节;5.给水排水;6.电气;7.
通信。
本标准由河北雄安新区管理委员会规划建设局负责具体技术
内容的解释,由河北雄安新区管理委员会改革发展局负责管理。
执行本标准过程中如有意见或建议,请寄送河北雄安新区管
理委员会规划建设局(邮寄地址:河北省雄安新区容城县白洋淀
大道153号;邮政编码:071700,电话:0312-5628203,邮箱:
xaxqrfgg@163.com),以供今后修订时参考。
本标准主编单位、主要起草人和审查人员名单:
主编部门:河北雄安新区管理委员会改革发展局
主编单位:河北雄安新区管理委员会规划建设局
中国建筑标准设计研究院有限公司
主要起草人:杨申武、董保强、赵贵华、张欣、刘培文、
卢泉岩、王官胜、王学超、刘霄、张瑞龙、
王国栋、袁代光、戚上上、石磊、张文虎、
鲍世福、刘志方、叶云鹏、廖丹、张鹏、
黄岩
审查人员:吴涛、王阳明、尹峰、戴建宁、刘紫强
4
目次
1总则·······································································1
2术语·······································································2
3建筑·······································································4
3.1一般规定·······························································4
3.2防护标准与选址·······················································6
3.3主体要求·······························································7
3.4出入口与通风口······················································11
3.5辅助用房······························································13
3.6平战转换及平时使用·················································15
4采暖通风与空气调节·················································16
4.1一般规定······························································16
4.2防护通风·········································································16
4.3空气调节·········································································18
5给水排水································································20
5.1一般规定······························································20
5.2生活给水······························································20
5.3排水···································································21
5.4洗消···································································21
5.5平战转换······························································22
6电气······································································23
6.1一般规定······························································23
6.2电源···············································································23
6.3控制与信号······································································25
5
6.4照明···············································································25
6.5线路敷设·········································································27
6.6接地···············································································27
6.7平战转换·········································································28
7通信······································································29
附录A各房间的最小使用面积及主要设施························30
本标准用词说明····························································32
引用标准名录·······························································33
附:条文说明·······························································34
6
Contents
1GeneralProvisions······················································1
2Terms······································································2
3Architecture······························································4
3.1GeneralRequirements··················································4
3.2ProtectionStandardandSite············································6
3.3MainPart·······························································7
3.4EntranceandVent·····················································11
3.5AuxiliaryRoom·······················································13
3.6FunctionConversionbetweenPeacetimeandWartime················15
4HeatingVentilationandAirConditioning··························16
4.1GeneralRequirements·················································16
4.2ProtectiveVentilation··················································16
4.3AirConditioning·······················································18
5WaterSupplyandDrainage···········································20
5.1GeneralRequirements·················································20
5.2WaterSupply··························································20
5.3Drainage·······························································21
5.4Decontamination·······················································21
5.5FunctionConversionbetweenPeacetimeandWartime················22
6Electrical·································································23
6.1GeneralRequirements·················································23
6.2PowerSupply··························································23
6.3ControlandSignal·····················································25
7
6.4Lighting·······························································27
6.5LineConstruction······················································27
6.6Grounding·····························································28
6.7FunctionConversionbetweenPeacetimeandWartime················28
7Communication·························································29
AppendixAMinimumUsableAreaandInternalFacilities·········30
ExplanationofWordinginThisStandard·······························32
ListofQuotedStandards···················································33
Addition:ExplanationofProvisions····································34
8
1总则
1.0.1为满足战时群众所需的日常食品和药品需要,加强食品和药
品分配过程中的储备和供应功能,确保战时防护安全和稳定,使人
民防空食品储备供应站和药品储备供应站工程设计符合安全、合理、
适用、经济等要求,制定本标准。
1.0.2本标准适用于新建或改建的人民防空食品储备供应站(以下
简称食品站)和药品储备供应站(以下简称药品站)工程设计。
1.0.3食品站和药品站设计必须贯彻“长期准备、重点建设、平战
结合”的方针,坚持人防建设与经济建设协调发展、与城市建设相
结合的原则,服务于“战时防空、平时服务、应急支援”的使命任
务。设计中应采取相应措施,使食品站和药品站工程建设在战备效
益的前提下,充分发挥社会效益和经济效益。
1.0.4食品站和药品站设计除应执行本标准外,尚应符合现行的有
关国家标准、行业标准的规定。
1
2术语
2.0.1人民防空食品储备供应站foodstorageandsupplystation
worksofcivilairdefence
简称食品站。是保障战时留城人员应急食品供应的人防工程,
主要承担战时食品的收货验收、整理、储存、检查、盘点、分配、
出库、信息管理等工作。
2.0.2人民防空药品储备供应站drugstorageandsupplystation
worksofcivilairdefence
简称药品站。是保障战时留城人员应急药品供应的人防工程,
主要承担战时药品的收货验收、整理、储存、检查、养护、盘点、
分配、出库、信息管理等工作。
2.0.3应急食品emergencyfood
战时方便食用且耐储存的食品。
2.0.4应急药品emergencydrug
战时卫生防疫、伤病员救护中使用的医用药品。
2.0.5防护区blastspace
人民防空工程中由与防护密闭门、防爆波活门相连接的临空
墙、外墙围合而成的区域。
2.0.6染毒区airtightlessspace
人防工程中能抵御预定的爆炸动荷载作用,但允许染毒的区
域。
2.0.7收货区receivingspace
2
到库食品或药品入库前核对、查验等作业的区域。
2.0.8储存区storagingspace
用专门器具或捆扎形式储存、保管食品或药品的区域。
2.0.9发货区shippingspace
食品或药品集中待运的区域。
2.0.10验收室acceptanceroom
存放相关仪器、设备或养护材料,在食品或药品验收入库、在
库检查、养护中,对食品或药品进行检查、监控的场所。
2.0.11辅助房间subsidiaryroom
战时生活设施、设备设施等辅助房间,包括通风、给排水、供
电、防化、通信等专业设备房间、厕所、盥洗室、水库、水箱间、
泵房、防化通信值班室、配电间、防化器材储藏室等。
2.0.12室外机防护室protectiveroomforoutsidesystem
装有空调室外机的专用房间。
3
3建筑
3.1一般规定
3.1.1食品站和药品站工程的任务和规模应分别符合下列规定:
1食品站主要承担战时食品的收货验收、整理、储存、检查、
盘点、分配、出库、信息管理等工作。食品站按不小于1500平方米
且不大于2000平方米的规模设置;
2药品站主要承担战时药品的收货验收、整理、储存、检查、
养护、盘点、分配、出库、信息管理等工作。药品站按不小于800
平方米且不大于2000平方米的规模设置。
3.1.2与食品站和药品站平时和战时功能无关的设备房间应设置在
防护区之外。穿过人防围护结构的管道应符合下列规定:
1与食品站和药品站无关的管道不应穿过人防围护结构;上
部建筑的生活污水管、雨水管、燃气管等不得进入食品站和药品站;
2当供水、消防、排水、供热、冷媒等管道穿过食品站和药
品站的顶板或临空墙时,其公称直径不宜大于150mm;穿过门框墙
时,其公称直径不应大于80mm;
3管道及其穿过的人防围护结构应采取防护密闭措施。
3.1.3食品站和药品站的防水设计应符合下列规定:
1食品站和药品站的防水设计不应低于现行国家标准《地下
工程防水技术规范》GB50108规定的防水等级一级标准;
2单建或结建形式的食品站和药品站其上部建筑范围内的顶
4
板均应采用防水混凝土,当有条件时宜附加一种柔性防水层。
3.1.4食品站和药品站的室内装修设计应符合下列规定:
1室内装修应选用防火、防潮的材料,并应满足防腐、抗震、
环保及其他特殊功能的要求,且应符合现行国家标准《建筑内部装
修设计防火规范》GB50222的规定;
2顶板的底面不应抹灰;平时设置吊顶时,应采用轻质、坚
固的龙骨,吊顶饰面材料应方便临战时拆卸;
3清洁区的顶棚材料应防止虫害和霉菌孳生,地面应平整防
滑,墙面、地面均应易于清洗;
4密闭通道、防毒通道、洗消间、滤毒室、除尘室、扩散室
等染毒区的房间、通道,其墙面、顶面、地面均应平整光洁,易于
清洗;
5除地下汽车库停车位部分外,设置地漏的房间和通道,应
采取防水、防滑的构造措施,并设排水坡坡向地漏。其楼地面宜低
于相邻楼地面15mm,并应采用不吸水、易冲洗、防滑的面层材料;
6柴油发电机房、通风机房、水泵间及其他产生噪声和振动
的房间,应根据其噪声强度和周围房间的使用要求,采取相应的隔
声、吸声、减振等措施。
3.2防护标准和选址
3.2.1食品站和药品站的防护级别和人员配置应按表3.2.1确定。
5
表3.2.1食品站和药品站的防护级别和人员配置要求
防核武器防常规武器
工程名称工程类型防化级别人员配置
级别级别
掘开式5
5
食品站土中坑、地道式乙不少于22人
4B
岩石中坑、地道式4
掘开式5
5
药品站土中坑、地道式乙不少于20人
4B
岩石中坑、地道式4
3.2.2食品站或药品站应按一个防护单元设计,可不划分抗爆单元。
其防护区的最大建筑面积不应大于2000m2。坑地道工程防护区最
大建筑面积可扩大30%。
3.2.3食品站和药品站的选址应符合以下规定:
1距离生产、储存易燃易爆物品厂房、库房不应小于50m;
距离有害液体、重毒气体的贮罐不应小于100m;
2应设置在进出方便和战时电源、水源有充分保障的地方;
3应避开城市重要目标;
4不应选择对食品有显著污染的区域;
5不应选择有害废弃物以及粉尘、有害气体、放射性物质和
其他扩散性污染源不能有效清除的区域;
6不宜选择易发生洪涝灾害的地区,难以避开时应设计必要
的防范措施。
3.2.4食品站和药品站宜单独修建,可与其他设施结合修建。
3.2.5食品站和药品站应与相邻人防工程或人防干道设置战时连通
口。
6
3.3主体要求
3.3.1食品站和药品站平面设计应做到功能分区合理,路线清晰,
运输方便,避免交叉。食品站平面布局流线应满足食品装卸-理货-
收货入库-验收-整理-储存-盘点分配-发货出库-食品装卸等工艺流程
的需要;药品站平面布局流线应满足药品装卸-理货-收货入库-验收-
整理-储存-养护-盘点分配-发货出库-药品装卸等工艺流程的需要。
3.3.2食品站和药品站应由装卸理货区、收货区、储存区、发货区、
口部用房、管理服务房间等功能分区组成。收货区、发货区可兼顾
设置,储存区与收货区、发货区应隔开布置。其中收货区、发货区
总面积不宜超过收货区、发货区、储存区面积之和的10%。每个分
区及房间的的最小使用面积及主要设施,应根据附录A确定。
3.3.3储存区、收货区、发货区按人工堆垛设计时净高不应小于
2.1m,使用叉车堆垛时净高不应小于3.0m。其他区域的净高不应小
于2.0m。
3.3.4食品站和药品站储存区可根据物品的储存条件设置普通库、
冷藏库,并配备必要的加热、冷藏等设施。
3.3.5普通库室内温度不做要求;冷藏库室内温度为2~10℃;各
库房相对湿度应保持在35~75%之间。
3.3.6食品站和药品站战时宜设置安全防范设施和仓库管理系统。
3.3.7装卸平台宜靠近坡道入口或物资垂直运输井。卸货平台设计
应符合下列规定:
1卸货平台宽度不应小于2.50m;当采用叉车搬运时宽度不应
小于4.00m;
7
2室外卸货平台上方宜设置雨篷,雨篷应高出运输车顶部至
少500mm,雨篷宽度宜超出卸货平台宽2.00m;
3卸货平台边缘顶面高出平台下地面0.70m~1.20m,可根据需
要设置高度调节板。
3.3.8收货区的设置应符合以下要求:
1应设有管理间和警卫室;
2采用叉车搬运时,应设有叉车充电间兼做叉车检修间;
3应设有不小于6m×6m临时堆放场地;
4与坡道入口或物资垂直运输口之间宜设有洞口不小于2.4m
×3m的供叉车通行的战时通行口,洞口两侧应设置防护密闭门和
密闭门各一道。
3.3.9储存区的设置应符合以下要求:
1储存区的面积和空间应与供应能力相适应,便于货架安置、
清洁消毒、物品存储及人员操作;
2储存区宜采用托盘或料箱形式。物品宜存放在托盘或货架
上,不应直接接触地面,宜采用机械化搬运。单个货架宽度为
0.30m~0.90m,宜两架并靠成组;
3贮存物品堆垛应与墙、屋顶(房梁)、库房散热器或供暖管道
的间距均不小于300mm,与地面的间距不小于100mm;
4通行理货的内部通道采用叉车搬运时不宜小于2.4m,采用
人工搬运时不宜小于1.5m;
5冷藏库要做到门窗严密、保温、不漏气;
6储存区内电瓶车行速不应超过75m/min,其通道尽头宜设置
不小于6m×6m的回车场地;
8
7储存区应设有不小于6m2的特殊物品库,专门存放有特殊
需要的食品或药品;
8食品站中原料、半成品
定制服务
推荐标准
- DB34/T 310022-2024 长大桥梁无人机巡检作业技术规程 2024-01-14
- DB3308/T 146-2024 乡村艺校建设指南 2024-03-08
- DB35/T 336-1999 鲻鱼苗种质量标准 1999-08-27
- DB35/T 580-2004 九孔鲍 种苗 2004-11-29
- DB35/T 338-1999 鲍苗种质量标准 1999-08-27
- DB35/T 532-2004 棕斑腹刺鲀、暗鳍腹刺鲀安全加工规范 2004-02-15
- DB3308/T 145-2024 衢陈皮生产技术规程 2024-01-22
- DB13/T 1189-2010 工业企业合同能源管理 2010-02-08
- DB3308/T 147-2024 艺术特色示范村建设规范 2024-03-08
- DB35/T 584-2004 九孔鲍 2004-11-29